Login:
Stimmen - 2, Durchschnittliche Bewertung: 4 ( )

Anleitung LST, modell B524IEFT-1

Hersteller: LST
Dateigröße: 97.07 kb
Dateiname: 77ba04c8-7e98-4f51-9ea8-c3d71713bfbe.pdf
Unterrichtssprache:en
Link zum kostenlosen Download Hinweise finden Sie am Ende der Seite



Anleitung Zusammenfassung


With the dual design, the input side or the output side isolator - depending on the location of the short circuit - interrupts the connection to the faulty loop segment. Therefore the detector remains in operation. Specifications Current consumption max. 100|jA (quiescent) Ambient temperature -30°C to +70°C Relative humidity 0 - 93% (no condensation) Dimensions 0 x H 102 x 26 (mm) Colour cream Weight 70g Approval VdS G200100 Order number 246013 Order name Isolator Detector Base/Anal./500/200/SS B524IEFT-1 Due to its robust multi-wire screw terminals, the detectors can be wired with ease, thus achieving a secure and durable connection. The base also provides a possibility for the easy connection of remote indicators. The base is designed for surface mounting in dry rooms. For special applications a range of accessories (for moist room, false ceiling or flush installation) is available. A mechanical theft protection of the detector can optionally be activated at the detector base. Building Safety. Building Security. © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX. +43 1 52114-27 OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED B524ÍEFT-1 DBL LST EN 0804.PDF • PAGE 1...


Bewertungen



Bewerten
Vorname:
Geben Sie zwei Ziffern:
capcha





Kategorien