Anleitung RCI, modell 10-175UL
Hersteller: RCI Dateigröße: 207.36 kb Dateiname: e25a34e5-e6da-42c6-9f21-2c9196291397.pdf
Unterrichtssprache:
|
|
|
|
Link zum kostenlosen Download Hinweise finden Sie am Ende der Seite
Anleitung Zusammenfassung
It must be installed in accordance with National and Local Electrical Codes and Regulations. Specifications • UL listed Access Control (UL294) • CSFM approved - California State Fire Marshal • MEA approved - NYC Dept. of Buildings 18-98-E • NFPA 101 (Life Safety) • Input 115VAC/60 Hz, .6 amps • Switch selectable 12VDC or 24VDC power limited output • 1.75 amps continuous supply current @ 12VDC or 24VDC • Latching fire alarm tie-in with manual reset • Filtered and electronically regulated output • Charge current: 0.4 amps Max • Aux relay output: (form “C”, 1 amp, 28VDC) • AC Fail output relay (form “C” 1 amp, 28VDC) • Enclosure Dimensions: 15.5”H x 12”W x 4.5”D Output Specifications Output VDC Switch Position Max. Stand-by Load DC Max. Alarm Load DC Battery (Optional) 12VDC SW1 Open 1.75 amps 1.75 amps 12VDC 24VDC SW1 Open 1.75 amps 1.75amps 24VDC Stand-By Specifications Output 4Hr. of Stand-by & 5 minutes of alarm 12VDC / 7 AH Battery Stand-by = 1.25 amps Alarm = 1.25 amps24VDC / 7 AH Battery 2 Installation Instructions The 10-175UL should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 as well as all applicable Local Codes. See Terminal Identification Chart on page 4 for a description of each terminal function. 1. Mount the 10-175UL in desired location. 2. Connect AC power (115VAC 60Hz) to the black and white flying leads of the transformer. Secure green wire lead to earth ground. Use 18 AWG or larger for all power connections (Battery, DC output). Use 22 AWG to 18 AWG for power limited circuits (trigger inputs, dry outputs). Keep power limited wiring separate from non-power limited wiring (115VAC/ 60Hz Input, Battery Wires). Minimum .25” (6.4mm) spacing must be provided. 3. Set the 10-175UL to the desired DC output voltage by setting switch SW1 to the appropriate position (power supply output specification table). Note: It is good operating practice to measure and verify output voltage before connecting devices to ensure proper operation of equipment. 4. Connect battery to terminals marked [+ BAT -] (battery leads included). Use two (2) 12VDC batteriesconnected in series for 24VDC operation. Note: For Access Control applications, batteries are optional. When batteries are not used a loss of AC will result in the loss of output voltage. When the use of standby batteries are desired, they must be lead acid or gel type. 5. Connect appropriate signaling notification devices to AC Fail supervisory relay outputs marked [N.C., N.O., C]. Note: To meet UL requirements, AC Supervisory outputs must be connected to the zone of Alarm Control Panel or to visual AC trouble indicator. 6. For Access Control Device & Fire Alarm Interface connections refer to desired Application Diagrams (pg. 6-8) and Terminal Identification Chart Maintenance Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level (see power supply output specifications chart). Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at battery terminal and at the board terminals marked [- BAT +] to insure there is no break in the battery connection wires. Note: Maximum charging current under discharges is 0.40 amps. Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed. 3 Terminal / Switch Identifcation: Terminal Legend Function/Description TRGI & TRG2 These input terminals are designed to connect to the normally closed outputs of an access control or fire alarm relay. These terminals control [LOCK+], and [STRIKE+], as well as 10-175UL output relay contacts [N.C., N.O., C] LOCK+ This terminal provides DC output voltage when [TRG1] and [TRG2] are shorted together and are typically used to power Mag Locks. STRIKE+ This terminal provides DC output voltage when [TRG1] and [TRG2] are unshorted and are typically used to power Electric Strikes. N.C., N.O., C Isolated dry Form “C” contacts. Shorting [TRG1] and [TRG2] together causes these contacts to switch. They are typically used for controlling multiple 10-175ULs with fire alarm tie-in (Fig. 4 and Fig. 5, pg. 7-8). AUX+ Continuous positive (+) DC power output voltage. It is not affected by TRG1, TRG2 operation. COM – Common negative (-) output (ground). FACP Spare wiring terminal used for fire alarm tie-in application (Fig. 1, pg. 6). BAT+, BAT – Stand-by battery connections. SW2 Momentary reset button (on front door) is used as a manual power supply reset after fire alarm system is restored. LED Diagnostics RED(DC) Green (AC) (Front Door) Power Supply Status ON ON Normal Function ON OFF Battery backup is powering output OFF ON No DC output OFF OFF Loss of AC. Discharged or missing stand-by battery. No DC output. 4 10-175UL SW1 VR1 + BAT --AC ACLOCK + STRIKE + COM -AUX + FACP AUX - NC NO C TRG1 TRG2 SW1 CLOSED -24V OPEN - ...