Login:
Stimmen - 3, Durchschnittliche Bewertung: 3 ( )

Anleitung Omega Engineering, modell I SERIES I/32

Hersteller: Omega Engineering
Dateigröße: 444.01 kb
Dateiname: 23Z010.pdf
Unterrichtssprache:en
Link zum kostenlosen Download Hinweise finden Sie am Ende der Seite



Anleitung Zusammenfassung


The display will stop flashing and show the top menu for Thermocouple types. If you press a controller will step to next menu item (Skip to Step 14). Step 11. Enter to the Thermocouple Type Input Submenu Press d to display flashing, previously selected Thermocouple type. Step 12. Scroll through available selection of TC types Press b to sequence thru flashing Thermocouple types, (select k -for type "K" CHROMEGA ® /ALOMEGA ® ) J KT E N DINJ R S B C - TCtypes J k t E N dNJ R S bC - Display Step 13. Store TC type After you have selected the Thermocouple type press d to store your selection, the instrument automatically advances to the next menu item. Step 14. Enter to Reading Configuration Menu The display shows RDG Reading Configuration, which is the top menu for 4 submenus: Decimal Point, Degree Units, Filter Constant and Input/Reading Submenus. Step 15. Enter to Decimal Point Submenu Press d to show DEC Decimal Point. Step 16. Display the Decimal Point position Press d again to display the flashing Decimal Point position. Step 17. Select the Decimal Point position Press b to select FFF. F Decimal Point position. Step 18. Store selected Decimal Point position By pressing d momentarily the Decimal Point position will be stored and the instrument will go to the next menu item. Step 19. Enter to Temperature Unit Submenu Display shows TEMP Temperature Unit. Step 20. Display available Temperature Units Press d to display the flashing Degree ° F or °C. Step 21. Scroll through Temperature Units selection Press b to select ° F Degree. Step 22. Store the Temperature Unit Press d to display momentarily that the Degree Unit has been stored and the instrument will go automatically to the next menu item. Step 23. Enter the Filter Constant Submenu Display shows FLTR Filter Constant Submenu. Step 24. Display the Filter Constant Value Submenu Press d to display the flashing, previously selected Filter Constant. Step 25. Scroll through available Filter Constants Press b to sequence thru Filter Constants 0001, 0002, 0004, 0008, 0016, 0032, 0064 and 0128. Step 26. Store the Filter Constant Press d momentarily to store 0004 Filter Constant and the instrument will automatically go to the next menu item. Step 27. Enter Alarm 1 Menu The display will show ALR1 the top menu for Alarm 1. In the following steps we are going to enable Alarm 1, Deviation, Unlatch, Normally Open, Active Above, Enable at power on and +2°F High Alarm i.e. Process Value > Setpoint 1 Value +2°F will activate Alarm 1. Step 28. Enter Alarm 1 Enable/Disable Submenu Press d to display flashing DSBL / ENBL. Step 29. Enable Alarm 1 Submenu If flashing ENBL is displayed, press a, if DSBL is displayed, press b until ENBL is displayed, then press d to store and go to the next menu item. Step 30. Select the Deviation Control Type Submenu Press d. If flashing _DEV Deviation is displayed press a, otherwise press b until flashing _DEV is shown. Now press d to store and go to next menu item. Step 31. Select the Latched Type Submenu Press d. If flashing UNLT Unlatched is displayed press a, otherwise press b until UNLT is displayed. Press d to store and advance to next menu item. Step 32. Select the Normally Open Type of Contact Closure Submenu Press d. If flashing N.o. Normally Open is displayed, press a, otherwise press b until N.o. is displayed. Press d to store and advance to next menu item. Step 33. Select the Above Type of Active Submenu Press d. If flashing ABoV Above is displayed, press a, otherwise press b until ABoV is displayed. Press d to store and advance to next menu item. Step 34. Enable Alarm 1 at Power On ( A.P.oN) Press d. If flashing ENBL is displayed, press a, otherwise press b until ENBL is displayed. Press d to store and advance to next menu item. Step 35. Enter Alarm 1 High Submenu Press a twice to skip ALR. L Alarm 1 Low value. ALR. L is for below & ALR. H for above. Step 36. Set the Alarm 1 High value ( ALR.H) Press d. Press b or c until value to set the display to 002.0. Press d to save. Step 37. Enter the Alarm 2 Menu The display will show ALR2 the top menu for Alarm 2. Repeat steps from 28 to 36 to set for Alarm 2 the same conditions as for Alarm 1. Step 38. Configuration of Display Color Selection Press a until the COLR Display Color Selection Menu appears on the Display. Configure COLR as N.CLR / GRN (green), 1.CLR / RED (red), 2.CLR / AMBR (amber). Please refer to the operator’s manual if needed. Step 39. Run a Test Press a until reset the controller and return to RUN Mode to display 075.0 (Ambient Temperature). Now you are ready to observe temperature as it rises 10°F higher than displayed. Touch the tip of the Thermocouple to raise the temperature above the Alarm 2 High value 082.0, and AL2 will turn on, and Display Color will change from Green to Amber. Continue touching the tip to raise the temperature above the Alarm 1 High value 087.0 and Display Color will change from Amber to Red. WARNING: These products are not designed for use in, an...


Bewertungen



Bewerten
Vorname:
Geben Sie zwei Ziffern:
capcha





Kategorien