|
Anleitung Zusammenfassung
• Use new black iron or steel pipe. Internally tinned copper or copper tubing can be used per National Fuel Gas Code, section 2.6.3, providing gas meets sulfide limits, and where permitted by local codes. • An ANSI approved 1/8” NPT pressure tapping point must be installed immediately upstream of the gas supply connection to the fireplace • A sediment trap may be install upstream of the fireplace to prevent moisture and contaminants from passing through to the fireplace control and burner. Failure to do so could prevent appliance from operating reliably. • On some local codes, the gas line must be connected to a gas shut-off valve recessed flush into the wall or floor outside the fireplace. The valve should be controlled by a removable valve key for safety. In this case, remove the shut-off valve from the flex line and installed direct to stub. WARNING Support the shut-off valve when attaching 1/2” gas line. Use a wrench to hold shut-off valve stationary. Do not twist the flex line when tightening the 1/2” gas line. WARNING Connecting directly to an unregulated propane/L.P.G. tank can cause an explosion. An external regulator must be used on all propane/LPG appliances to reduce the supply tank pressure to 13” w.c. (maximum). WARNING Do not connect directly to natural gas 1/2-psi or 2-psi systems. Always make sure the natural gas pressure is regulate to 10.5 w.c. (maximum) before operating the unit. 1. Check gas type. The gas supply must be the same as stated on the appliance’s rating decal. If the gas supply is different from the fireplace, STOP! Do not install the appliance. Contact your dealer immediately. 2. To ease installation, a 30” flex line with manual shut-off valve has been installed on this fireplace. Install 1/2” gas line onto shut-off valve. 3. Locate the gas line access hole in the outer casing of the fireplace. Remove the screw on the gas line cover plate. Open the fireplace door, insert the gas supply line through the knock out hole on the gas line cover plate, and connect it to the shut-off valve. 4. After completing gas line connection, purge air from gas line and test all gas joints from the gas meter to the fireplace for leaks. Use a soap and water solution or a gas sniffer. 5. To check gas pressure at valve, turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point. Refer to Figure 19: Gas Pressure Check at Gas Valve. After taking pressure reading, be sure and turn captured screw clockwise firmly to re-seal. Do not over torque. Check for gas leaks. WARNING Do not use open flame to check for gas leaks. 19 G GGA AAS SS L LLI IIN NNE EE A AAN NND DD E EEL LLE EEC CCT TTR RRI IIC CCA AAL LL I IIN NNS SST TTA AAL LLL LLA AAT TTI IIO OON NN Figure 19: Gas Pressure Check at Gas Valve Electrical Wiring: CAUTION Electrical connections should only be performed by a qualified, licensed electrician. Main power must be off when connecting to main electrical power supply or performing service. All wiring shall be in compliance with all local, city, and state codes. The appliance, when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70 (latest edition) Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operations. Verify proper operation after servicing. Standing Pilot Ignition Wiring-Millivolt Control: WARNING Do not connect 110-120 VAC to the Remote Wall Switch, DC Remote Control or the Millivolt Control Valve. The appliance will malfunction or the valve will be destroyed. Remote Wall Switch A remote wall switch and fifteen (15) feet of 18 Ga. wire are provided as standard with this fireplace. The wire has been pre-wired at the valve and routed through the right side, outer shell. (Access is also available on the left side through the square hole on that side). Position the wall switch inside of a junction box (not provided) at the desired location on the wall. Refer to Figure 20: Wiring Diagram for Standing Pilot Millivolt System. Do not extend beyond the wall switch wire length provided. NOTE Extended lengths of wire may cause the fireplace not to function properly. Longer length of wire is permitted if the wire is made out of larger gauge (diameter) wire. Always check with local code 20 GAS LINE AND ELECTRICAL INSTALLATION 21 Figure 20: Wiring Diagram for Standing Pilot - Millivolt System Figure 21: Schematic Diagram for Millivolt System G GGA AAS SS L LLI IIN NNE EE A AAN NND DD E EEL LLE EEC CCT TTR RRI IIC CCA AAL LL I IIN NNS SST TTA AAL LLL LLA AAT TTI IIO OON NN Optional Fan/Blower Systems The junction box for the fan/blower systems has been factory installed. This system requires that 110-120 VAC to be wired to the factory installed junction box before the fireplace is permanently installed. Refer to the figures below for wiring or schematic diagram. Figure 22: Blower Wiring Diag...
Dieses Handbuch ist für folgende Modelle:Andere Home Zubehör - 3000 SERIES (893.05 kb)