Hersteller: Macurco
Dateigröße: 71.12 kb
Dateiname: f57769eb-6035-4106-a800-671f1017f4be.pdf
|
Anleitung Zusammenfassung
NOTE: Any time the words “Control Panel” or “Alarm Panel” or “Alarm Control Panel” are used in these instructions, what is meant is a UL Listed Fire or Fire/Burglar or Critical Process Management Equipment. Alarm control panels that work on 12 or 24 VDC can provide battery backup to the CM-S1 detectors. This carbon monoxide detector is designed to detect CO gas from ANY source of combustion. It is NOT designed to detect smoke, fire or any other gas. LOCATION There are two usual sources of CO in homes -- defective heat sources (furnaces or wood burning stoves) and automobiles running in adjoining garages. The CM-S1 can provide protection from these sources, as well as any other sources of CO. For best protection, mount a CM-S1 in the hallway near each bedroom area. In addition, another CM-S1 may be mounted just inside the door from the adjoining garage. Consider placing another detector in a bedroom that is adjacent to a furnace room. Do NOT mount the unit in the garage. Do NOT mount the CM-S1 where the normal ambient temperature is below 40° F (4.4° C) or exceeds 100° F (37.8° C), or within 5 feet (1.5 meters) of a cooking appliance. SPECIFICATIONS Voltage: 12-24 VDC Current (standby/alarm @ 12-24V): 20mA/40mA (250 mA peak for 14ms/sec) Size: 3 1/8” x 5 1/8” x 1 .” Power (standby/alarm @ 12V): . Watt / . Watt Shipping Weight (each): One pound Power (standby/alarm @ 24V): . Watt / 1 Watt Alarm Relay: SPDT, 1 Amp, 60 VDC, 60 VA Operating Temperature Range: 32° to 120° F Alarm Setting: Per UL 2034 Buzzer Rating: 85 dBA at 10 Feet Color: White INSTALLATION See wiring diagram on page 4 for information on connections of the CM-S1. Macurco recommends a minimum of 22 AWG wire for runs up to 200 ft., and 18 AWG wire for longer runs. Mount the CM-S1 at the height that people breath: 4 to 5 feet (1.2 to 1.5 meters) above the floor. The unit can be placed vertically or horizontally on a wall, so the information on the front of the CM-S1 can be read in a normal manner. The word UP and a directional arrow on the internal cover indicate the correct mounting orientation of the detector. A rear housing enclosure is included with the CM-S1 faceplate. This enclosure configuration allows the unit to mount-flush on a wall. Wiring is routed through an access area on the base of the rear housing. A thin mid-plate enclosure component is also supplied with the CM-S1. This mid- plate component is used to mount the CM-S1 on a 2 x 4 single-gang, or “handy” electrical box, provided by the installer. The CM-S1’s faceplate component (with the detector attached) is then mounted on the mid-plate component. Electrical connections to the CM-S1 are made via the supplied five-conductor pigtail cable. The pigtail cable is first connected to the control panel wiring by means of wire nuts (refer to wiring diagram on page 4 for proper pigtail wiring). The pigtail cable’s connector then snaps into the mating connector on the back of the CM-S1 PCA, allowing easy installation and replacement of it. For proper detector operation, ensure that the CM-S1 is connected to a continuous source of power (not controlled by a wall switch). The CM-S1 power consumption figures represent worst-case conditions and will vary as the applied DC voltage varies. The alarm relay of the CM-S1 is a dry contact and rated at 1 Amp, 60 VDC, 60 VA. It is not suitable for fan control use. When connecting the units to remote buzzers or other devices (all buzzers or "other devices" must be UL approved), make sure that the load does not exceed the relay’s rating. External buzzers must be capable of generating a sound output greater than 85 dBA at 10 ft. Document #679-800-001 Page 1 of 4 Rev. 1.1, Jan 9, 2006 OPERATING INSTRUCTIONS When the detector is first powered, the status light will alternate between RED and GREEN as the unit performs a 2-1/2 minute warm-up cycle and self-test procedure. The buzzer on the CM-S1 will cycle twice, emitting its characteristic 4-chirp tone. At the end of this 2-1/2 minute cycle, the status light will turn GREEN to indicate normal operation and safe air. The alarm relay is not energized during the 2-1/2 minute warm-up cycle. The CM-S1 continuously monitors the air. If the CM-S1 measures levels of CO greater than the danger level, the RED light will turn on, the Alarm Relay will switch to actuate the alarm circuits in the control panel, and the buzzer on CM-S1 units will sound. The computer in the CM-S1 is programmed to alarm if the danger levels of carbon monoxide are exceeded, which are time and concentration-related. The alarm points are: 70 ppm of CO after 60 to 240 minutes, 150 ppm of CO after 10 to 50 minutes, and 400 ppm of CO after 4 to 15 minutes, in accordance with the provisions of UL Standard 2034. WHEN AN ALARM OCCURS (INSTALLER NOTE: It is recommended the following information below be posted near the control/alarm panel or a copy provided to the customer.) ! WARNING: Actuation of your CO alarm indicates the presence of carbon monoxid...