Login:
Stimmen - 3, Durchschnittliche Bewertung: 3.3 ( )

Anleitung Attwood, modell 99520-1

Hersteller: Attwood
Dateigröße: 123.25 kb
Dateiname: carbon-canister-installation.pdf
Unterrichtssprache:en
Link zum kostenlosen Download Hinweise finden Sie am Ende der Seite



Anleitung Zusammenfassung


A proper location in the hull must be identified and dedicated for the installation of the canister. • The hose connections to the canister must be accessible for inspection and service. • The canister should not be mounted in a location where it will be stepped on or otherwise have a force exerted upon it. • The canister can be mounted at any orientation from horizontal to vertical provided that the vent side port is not lower than the tank side port when boat is in either static floating or trailering position. • The vent line before and after the canister must be “self draining”. • If mounted in the engine compartment, the canister must have a heat shield (will be integrated into the canister and sold as one unit). • Canister must be mounted higher than the highest point of fuel tank to allow for proper line draining. Fasteners Mount securely with (2) W bolts or #14 screws through each mounting tab hole. Rubber isolators are provided with each canister to allow for convenient installation. Vent Line Secure 5/8" vent hose with a clamp over each port (not included). Secure the vent hose as needed with hose mounting clamps for proper routing of hose and to ensure there is not stress on the hose at the connection to the canister. Integrated System Requirements Liquid fuel is not permitted to enter the canister. This can be managed by installing an in-line surge protector vertically +/- 45° as close to the tank as possible. There must be no less than 24" of hose between the inline surge and the canister all of which must be self draining to the tank. Liquid water must not enter the canister from the exterior of the vessel. This can be managed by installing a P-trap or similar device at the vent hardware mounted to the hull. Ullage must be designed into the integrated tank to allow a minimum of 5% of the tanks total volume to remain unfilled with fuel. This allows for the safe expansion of the fuel during a system increase in temperature. © Copyright 2008, Attwood Corporation. Lowell, MI....

Dieses Handbuch ist für folgende Modelle:
Boote Zubehör - 99510-1 (123.25 kb)
Boote Zubehör - 99515-1 (123.25 kb)
Boote Zubehör - 99530-1 (123.25 kb)
Boote Zubehör - 99540-1 (123.25 kb)

Bewertungen



Bewerten
Vorname:
Geben Sie zwei Ziffern:
capcha





Kategorien