Login:
Stimmen - 2, Durchschnittliche Bewertung: 4 ( )

Anleitung Majestic Appliances, modell UVSRC42

Hersteller: Majestic Appliances
Dateigröße: 182.79 kb
Dateiname:
Unterrichtssprache:en
Link zum kostenlosen Download Hinweise finden Sie am Ende der Seite



Anleitung Zusammenfassung


Attach the cover to the face of the EB1 while being careful to position the excess wire completely within the EB1. Attach the coverplate to the firebox. (Fig. 7) Inside Fig. 7 Junction box (EB-1) hook-up. FP580 Front of Unit Electrical Box Front of Unit Outside (Left Side) 20002068 UVSRC Series Fireboxes Fig. 8 Wiring diagram. FP579 Black White Ground Fan Install Fan Kit Assembly Refer to the Fan Kit (Model FK12) installation instruc tions for field installation. (Fig. 8) WHEN INSTALLED, THE FIREBOX MUST BE ELCTRICALLY CONNECTED AND GROUNDED (See Figure 14) IN ACCORDANCE WITH LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES: U.S. INSTALLATIONS — Follow local codes and the National Electrical Code ANSI/NFPA No. 70. Cold Climate Insulation In cold climates, insulation of the enclosure around the firebox is suggested to avoid problems with cold air. Insulating the enclosure around the firebox is recommended, but not a requirement. The following steps are suggested to minimize cold air problems. Insulate the base of the firebox with a noncombustible insulation. This step is particularly important for outside wall installations over concrete slab floor construction. If a platform is used to raise the firebox, the insulation should be placed on top of the platform before the firebox is set. (Fig. 9) Refer to Page 5, Figure 3 for minimum clearances to combustibles. Inspect joints of the firebox as well as the points of sealing between the firebox and the finishing materials. Any cracks should be sealed with noncombustible caulking or insulation. Refer to Figures 9 and 10 for details of sealing between the firebox and finishing materials. When a firebox is installed in a chase or on an outside wall, the enclosure should be insulated like any other outside wall of the home. Plywood or hardboard may be placed on the standoffs and insulation placed on this surface. (Fig. 10) Noncombustible insulation, such as vermiculite, Pearlite, Zonalite or unfaced fiberglass insulation, may be used between the exterior of the firebox and chase drywall up to 1" from the top of the firebox. FP607a Fig. 9 Insulation between firebox and platform. Hard Flat Surface Insulation Platform FP608a Insulation Plywood Support Fig. 10 Additional insulating methods. Finishing Refer to Page 5, Figure 3 for allowable finishing materi- als and clearances to combustibles. All joints, top, bottom and sides, where the wall or decorative facing material meets the firebox surround must be completely sealed with a noncombustible material. (Figs. 11-14) Finishing Refer to Page 5, Figure 3 for allowable finishing materi- als and clearances to combustibles. All joints, top, bottom and sides, where the wall or decorative facing material meets the firebox surround must be completely sealed with a noncombustible material. (Figs. 11-14) UVSRC Series Firebox Finished Wall Must be sealed with noncombustible material Noncombustible Decorative Facing 2 x 4 Finished Header Standoff NOTE: Do not install combustible materials on any of the black fireplace surround. Hearth Extension A hearth extension may be used but is not required for these fireboxes. A raised hearth extension may be used as shown in Figure 15. Fig. 11 Sealing spaces between appliance and finishing FE107 Noncombustible Caulking/Insulation 2 x 4 Framing Finishing MaterialStandoff 20002068 materials. Fig. 12 Surround flush with finished wall. FP568a ..." See mantel drawing for shelf-to-surround dimension Mantel Shelf Finished Wall Stud 2 x 4 Standoff Seal with noncombustible material ONLY Surround Fireplace Front 2 x 4 Stud Finished Wall May be sealed with noncombustible materialFireplace Front Top View Side View Surround FP610a 9 Fig. 14 Facing on firebox flush with finished wall. FP611a Finished Wall Noncombustible Decorative Facing Surround 2 x 4 Finished Header Covered Wall Must be sealed with noncombustible material Standoff FP612b Fig. 15 Side view of firebox with raised hearth extension. Fig. 13 Appliance surround flush with finished wall. Hearth Brick Hearth Extension Surround Noncombustible Hearth Extension Combustible Platform UVSRC Series Fireboxes Install Hood A hood is furnished with the firebox. Optional hoods listed on Page 12 may be installed as shown in Figures 16 and 17. Failure to do so may create a fire hazard. WARNING: When the black surround is covered by a brick surface, (Figure 16), use an extended hood. The hood should extend out to the brick surface (Figures 16 and 17) and be attached to the firebox. The maximum brick to noncombustible surface that may extend out past the black surround surface is 4...". Maintenance Keep the control compartment, logs and burner area surrounding the logs clean by carefully vacuuming or brushing at least twice a year or as necessary. THE LOGS CAN GET VERY HOT — HANDLE ONLY WHEN COOL. Always turn off the gas to the pilot before cleaning. For relighting, refer to the lighting instructions located on the Rating Plate of the gas log set. Never obstruct...

Dieses Handbuch ist für folgende Modelle:
Kamine - UVSRC36 (182.79 kb)

Bewertungen



Bewerten
Vorname:
Geben Sie zwei Ziffern:
capcha





Kategorien