Login:
Stimmen - 5, Durchschnittliche Bewertung: 4.2 ( )

Anleitung Napoleon Fireplaces, modell SSDVST-CNE-B

Hersteller: Napoleon Fireplaces
Dateigröße: 4.94 mb
Dateiname:
Unterrichtssprache:en
Link zum kostenlosen Download Hinweise finden Sie am Ende der Seite



Anleitung Zusammenfassung


Install the roof flashing -Extend the vent sections through the roof structure. Install the roof flashing over the vent section and position such that the vent column rises vertically (use carpenters level -see Figure 25). Nail along perimeter to secure flashing or adjust roofing to overlap the flashing edges at top and sides only and trim where necessary. Seal the top and both sides of the flashing with waterproof caulking. J. Install the storm collar -Install the storm collar, supplied with the flashing, over the vent / flashing joint. See Figure 25. Loosen the storm collar screw. Slide collar down until it meets the top of the flashing. Tighten the adjusting screw. Apply non-combustible caulking or mastic around the circumference of the joint to provide a water tight seal. NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Figure 25 Storm Collar Flashing K. Install the vertical termination - The final Step involves installation of the SV4.5CGV-1 Vertical Termination. Extend the vent sections to the height as shown in the "Vertical vent termination section" (Page 6, Figure 4B). The SV4.5CGV-1 Vertical Termination (Figure 26) can be installed in the exact same fashion as any other Secure Vent™ section. Align the termination over the end of the previously installed section, adjusting the radial alignment until the four locking dimples of the termination are aligned with the inlets of the four incline channels of the last vent section. Push the termination down until it fully engages, then twist the termination clockwise running the dimples down and along the incline channels until they are seated at the end of the channels. Figure 26 If the vent system extends more than 5 feet (1.5 m)above the roof flashing, stabilizers may be necessary. Additional screws may be used at section joints for added stability. Guide wires may be attached to the joint for additional support on multiple joint configurations. NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 17 H V V1 V H Table A H Maximum V Minimum feet (meter) feet (meter) 2 (0.610) 1 (0.305) 4 (1.219) 2 (0.610) 6 (1.829) 3 (0.914) 8 (2.438) 4 (1.219) V + H = 40 feet (12.2 meters) Max. H = 8 feet (2.4 meters) Max. Ratio V to H ratio is 1:2 Table B H Maximum V Minimum feet (meter) feet (meter) 5 (1.524) Elbow Only 5 (1.524) 1 (0.305) 10 (3.048) 2 (0.610) 15 (4.572) 3 (0.914) 20 (6.096) 4 (1.219) V + V1 + H = 40 feet (12.2 m) Max. H = 20 feet (6.096 meters) Max. Figure 28- Side Vent - ONE 90 DEGREE ELBOW Figure 27 - Top Vent - STRAIGHT Figure 29 - Top Vent - TWO 90 DEGREE ELBOWS u Ceiling Firestop / Spacer (SV4.5VF) u Ceiling Firestop / Spacer (SV4.5VF) vWall Firestop/ Spacer (SV4.5HF) A Vent Restrictor, as shown in Figure 17 on Page 13, must be used in this application uCeiling Firestop / Spacer (SV4.5VF) u When using Secure Flex, use Firestop / Spacer SF4.5VF 40 feet (12.2 meters) Maximum u When using Secure Flex, use Firestop / Spacer SF4.5VF Example: If 8 feet of (H) horizontal vent run is needed, then 4 feet minimum (V) vertical vent will be required. This table shows a 1(V) to 2(H) ratio. For every 1 foot of (V) vertical, you are allowed 2 feet of (H) horizontal run, up to a maximum horizontal run of 8 feet. u When using Secure Flex, use Firestop / Spacer SF4.5VF. v When using Secure Flex, use Firestop / Spacer SF4.5HF. Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required. This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet. An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system. See Figure 36. VERTICAL VENT FIGURES/TABLES Notes: • Secure Vent™ (rigid vent pipe) is shown in the Figures; Secure Flex™ (flexible vent pipe) may also be used. • It is very important that the horizontal/ inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of 1/4" rise per foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level. • SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible wall. • Two 45 degree elbows may be used in place of one 90 degree elbow. The same rise to run ratios, as shown in the venting Figures for 90 elbows, must be followed if 45 degree elbows are used. • AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM (See Figure 36). WARNING Under no circumstances, may separate sections of concentric flexible vent pipe be joined together. VERTICAL VENT FIGURES / TABLES (CONTINUED) Table D H + H1 Maximum V Mi...

Dieses Handbuch ist für folgende Modelle:
Kamine - SSDVPF-CNE-B (4.94 mb)
Kamine - SSDVPF-CNE-B (4.94 mb)
Kamine - SSDVPF-CNE-B (4.94 mb)
Kamine - SSDVPF-CNE-B (4.94 mb)

Bewertungen



Bewerten
Vorname:
Geben Sie zwei Ziffern:
capcha





Kategorien