Login:
Stimmen - 5, Durchschnittliche Bewertung: 3.8 ( )

Anleitung Thermo Products, modell OC2-56

Hersteller: Thermo Products
Dateigröße: 1.31 mb
Dateiname: 319c96b2-536b-497e-ad55-b72be2433dca.pdf
Unterrichtssprache:en
Link zum kostenlosen Download Hinweise finden Sie am Ende der Seite



Anleitung Zusammenfassung


PLATE PART NO. TOP-25752 BTM-35733 35750 35750 35750 35750 MTG. PLATE GASKET PART NO. 330090 330088 330088 330088 330088 **NOZZLE SIZE .50-60A .60-60A* .75-60A* .90-60A* 1.10-60A* NOZZLE PART NO. 380393 380394 380395 380396 380397 OIL PUMP PRESSURE 170 PSI 145 PSI 145PSI 145 PSI 150PSI BURNER F3 F3 F5 F5 F5 BURNER PART NO. 380215 380215 380216 380216 380216 * A refers to hollow pattern nozzle ** NOTE: The reason the Riello burner nozzle sizes are smaller than the standard Thermo Pride burner nozzles is that pre-set pump pressures are higher, therefore achieving the same firing rate with a smaller nozzle. For more specific burner information, specifications or service information, reference the training manual enclosed with each Riello burner or contact: Riello Corporation of America, 5 Pond Park Road Hingham, Massachusetts 02043 (617) 749-8292 I. HEAT EXCHANGER CLEANING INSTRUCTIONS: . WARNING: THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON. It is important to inspect and clean the heat exchanger once a year, or as necessary, to remove any build-up of soot. A layer of soot on the inside of the heat exchanger will act as an insulator and reduce heat transfer, resulting in less efficiency. To clean the heat exchanger, first turn off all power to the unit. Next, remove the access panel (see below and beginning of following page) immediately above the burner (on the horizontal furnace, it will be located to the side of the burner) to gain entry to the clean-out covers, refer to figure 15. This panel is identified with a label. Remove clean-out covers, the vent connector pipe to the chimney, the burner, and the burner mounting plates. When removing the clean-out covers, special care must be taken not to damage the gaskets. Should the gaskets separate, crack, break, or be unsuitable for reuse, the gasket must be replaced before reattaching the clean-out covers. 11 All installations and services must be performed by qualified service personnel. 12 Fig. 15: Typical Heat Exchanger Cleanout Cover Locations. With access to the inside of the heat exchanger through the burner area, clean-out openings, and vent pipe connection, it is possible to use a long, flexible wire brush and an industrial type vacuum cleaner to remove any soot build-up. NOTE: A one inch (outside diameter) vacuum cleaner hose will fit into the radiator. To vacuum and brush the outer radiator of the heat exchanger, go through the clean-out openings in both directions, as shown in figure 16, below. Fig. 16: Recommended method and device for cleaning inside of heat exchanger. Reassemble the furnace to its original construction. Remount the burner being certain that the air tube is properly inserted into the chamber opening (see section E). If heavy soot deposits were found in the heat exchanger, this may indicate the burner is out of adjustment. III. USERS INFORMATION SECTION A. OIL SUPPLY: Do not allow the fuel tank to run completely empty. During the summer, keep the tank full to prevent condensation of moisture on the inside surface of the tank. If the fuel tank runs completely dry, it may be necessary to purge the lines of trapped air. Contact a qualified technician to bleed the lines and restart the burner. OIL SUPPLY VALVE: Turn the oil supply valve off if the burner is shut down for an extended period of time. B. COMBUSTION AIR SUPPLY: The burner requires a generous amount of clean combustion air to operate safely. Lack of adequate combustion air can result in erratic operation of the burner, noisy combustion, or fuel odors in the air. NEVER BLOCK THE FURNACE FROM THE SUPPLY OF COMBUSTION AIR. If there is an exhaust fan, dryer or return air grill in the furnace room, there should be increased concern and additional efforts may be required to provide adequate combustion oil to the furnace at all times. All installations and services must be performed by qualified service personnel. C. INSPECTION AREAS VESTIBULE: The furnace vestibule area or burner compartment should be inspected by removing the front door of the furnace and looking for signs of excessive heat such as discoloration of components materials damage, from rust or corrosion, soot or carbon build-up. EXTERIOR OF FURNACE: The furnace exterior should be inspected for signs of excessive heat such as discoloration of materials and damage from rust or corrosion. FLUE PIPE, VENT PIPE OR CONNECTOR: The furnace vent pipe should be inspected for signs of rust, corrosion pitting or holes in pipe, and leakage around seams in pipe, indicated by soot or condensate streaks. CHIMNEY OR VENTING SYSTEM: The furnace venting system should be inspected for signs of rust, corrosion pitting or holes, and signs of condensation or moisture leakage from the venting system. If any of the above sympto...

Dieses Handbuch ist für folgende Modelle:
elektrische Heizungen - OH11-105 (1.31 mb)
elektrische Heizungen - OC5-85 (1.31 mb)
elektrische Heizungen - OH16-125 (1.31 mb)
elektrische Heizungen - OH2-56 (1.31 mb)

Bewertungen



Bewerten
Vorname:
Geben Sie zwei Ziffern:
capcha





Kategorien