Login:
Stimmen - 4, Durchschnittliche Bewertung: 4 ( )

Anleitung Generac, modell 0047210, 0047220, 0047230, 0047240, 0047250, 0047251, 0047252, 0047253, 0047260

Hersteller: Generac
Dateigröße: 3.43 mb
Dateiname: 87a29ac1-81df-4ff4-b793-c283504fcf94.pdf
Unterrichtssprache:en
Link zum kostenlosen Download Hinweise finden Sie am Ende der Seite



Anleitung Zusammenfassung


Be sure to read the “Safety Rules” on Pages 2 and 3, as well as all other safety information in this manual, before attempting to operate this (and related) equipment. • 2.11.1 PRIOR TO INITIAL START-UP ! Prior to initially starting the generator, it must be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quantities of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure. Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to Section 4, “Maintenance.” Generac® Power Systems, Inc. 11 Section 3 — Operation Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators • 2.11.2 TRANSFER SWITCH If this generator is used to supply power to any electrical system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents electrical backfeed between two different electrical systems. (For additional information, see the applicable transfer switch manual for this unit.) The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compliance with applicable codes, standards and regulations. • 2.11.3 FUEL SYSTEM Make sure the fuel supply system to the generator (a) delivers the correct fuel at the correct pressure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See “Specifications” (Section 1.10) for more information. • 2.11.4 GENERATOR SET LUBRICATION Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” (Section 1.10) and “Engine Oil Recommendations” (Section 1.14). NOTE: This engine is shipped from the manufacturer with 15W-40 oil. This oil should be changed after 30 hours of operation. • 2.11.5 ENGINE COOLANT Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” (Section 1.10) and “Coolant” (Section 1.15). • 2.11.6 BELT TENSION Check the engine fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approximately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8inch (10 to 16 mm). • 2.11.7 ELECTRICAL SYSTEM Make sure the generator is properly connected to an approved earth ground and/or ground rod. Make sure the generator battery is fully charged, properly installed and interconnected, and ready for use. Check to ensure that there are no loose electrical connections. Restrain any loose wires to keep them clear of any moving generator set components. 3.1 USING A STANDARD “GTS” TRANSFER SWITCH When required, the pre-packaged standby generator can be installed with a standard Generac “GTS” type engineered automatic transfer switch. When a GTS type transfer switch is used, it controls automatic operation and automatic transfer as follows: • Solid state circuits in the transfer switch monitor utility power source voltage. • When utility source voltage drops below a pre-set level, transfer switch action closes the circuit. The engine then cranks and starts as controlled by the pre-packaged generator’s Control Module circuit board. • After the engine starts and when the generator AC output voltage and frequency have reached a pre-set value, transfer switch circuits signal the transfer switch main contacts to actuate to the “STANDBY” power source side. Generator AC output then powers load circuits. • When the utility power source voltage is restored above a pre-set level, transfer switch solid state circuits signal the switch main contacts to move back to their utility power source side. • Following re-transfer back to the utility power source side, transfer switch circuit board action opens the circuit. Engine then shuts down. NOTE: If the generator is installed in conjunction with a standard GTS type transfer switch, refer to the applicable transfer switch manual for exact operating parameters and timing sequences. 3.2 CONTROL CONSOLE COMPONENTS The components of a liquid-cooled generator control console (Figure 3.1) are as follows: Figure 3.1 - Liquid-Cooled Generator Panel FUSE FAULT HOUR METER 15-A INDICATOR AGC AUTO SET EXERCISE OFF TIME ON MANUAL 12 Generac® Power Systems, Inc. Section 3 - Operation Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators • 3.2.1 HOURMETER Indicates time the engine-generator has operated, in hours and tenths of hours. Use the hourmeter along with the periodic maintenance schedule for the generator set. • 3.2.2 AUTO/OFF/MANUAL SWITCH Use this three-position switch as follows: • Set the switch to AUTO...


Bewertungen



Bewerten
Vorname:
Geben Sie zwei Ziffern:
capcha





Kategorien